Description
Product Description
-
Turnkey, containerised MV PV inverter station built on the SG4400UD-MV platform with advanced three-level inverter technology for high efficiency and reliability.
-
Engineered for 1500 V DC high-voltage PV system compatibility with multiple independent MPPTs to maximise energy harvest from solar fields.
-
Integrated MV transformer steps up low-voltage AC to 33 kV for direct grid connection, with built-in MV switchgear and LV auxiliary power supply.
-
Modular design simplifies transport, installation, service and maintenance while housing protections and control systems in a 20-foot container footprint.
-
Includes grid support functions such as low/high voltage ride-through (L/HVRT), active/reactive power control and power ramp rate control to satisfy grid code requirements.
-
Comprehensive protection and monitoring features cover DC/AC protection, surge protection, insulation and ground-fault monitoring, and optional “Q at night” support.
Technical Specifications
DC (PV) Input
-
Maximum PV input voltage: 1500 V DC.
-
MPP voltage operating range: ~895 V – 1500 V.
-
Number of independent MPPTs: 4.
-
Number of DC inputs: 20 (optional up to 28).
-
Maximum PV input current: 4 × 1435 A.
AC (Output) / Power Ratings
-
Rated AC output power: ~4400 kVA @ 45 °C.
-
Maximum AC power: up to ~5060 kVA (at lower ambient temperatures).
-
Nominal medium-voltage output level: 33 kV (configurable within 10 kV–35 kV).
-
Maximum AC current: ~292.2 A.
-
Power factor: > 0.99 nominal; adjustable 0.8 leading to 0.8 lagging.
-
Grid frequency: 50 Hz (45–55 Hz) and 60 Hz (55–65 Hz) variants.
Efficiency & Performance
-
Maximum inverter efficiency: ~99 %.
-
European (weighted) efficiency: ~98.7 – 98.8 %.
-
Total harmonic distortion (THD) < 3 % at nominal power.
Transformer & Grid Interface
-
Integrated MV transformer with step-up from LV to 33 kV.
-
Transformer vector: typically Dy11 (common configuration).
-
Transformer cooling: ONAN (oil-natural, air-natural).
Protection & Grid Support
-
DC input protection: load break switch + fuse.
-
Inverter output and AC MV output protection: circuit breakers.
-
Surge protection: DC Type II and AC Type II.
-
Grid monitoring, ground-fault monitoring, insulation monitoring and overheat protection.
-
Grid support functions: L/HVRT, active/reactive power control, ramp rate control and optional Q-at-night.
Physical & Environmental
-
Tank/container dimensions: ~6058 × 2896 × 2438 mm (20-foot standard).
-
Protection degree: Inverter IP65; other components IP54 (typical).
-
Operating ambient temperature: −35 °C to +60 °C (derating above ~45 °C).
-
Relative humidity range: 0 %–100 % non-condensing.
-
Cooling method: temperature-controlled forced air.
-
Maximum standard operating altitude: ~1000 m (higher with options).
-
Auxiliary power supply: ~15 kVA (optional up to 40 kVA).
Communications & Monitoring
-
Displays: LED and WebHMI/status indicators.
-
Communication interfaces: RS485, Ethernet; optional optical fibre.
Compliance & Standards
-
Conforms to CE and international standards including IEC 62109, IEC 61727, IEC 62116, IEC 62271-202, IEC 62271-200 and IEC 60076 among others.








Reviews