Description
Product Description
-
Turnkey medium-voltage PV inverter station engineered for large grid-connected solar power plants, supporting up to approximately 4.48 MVA AC output.
-
Based on Sungrow’s SG4400UD-MV platform with advanced three-level inverter technology for high efficiency and reliability.
-
Designed for high-voltage DC 1500 V PV input systems and multiple independent MPPTs to optimise energy yield.
-
Integrated MV transformer (stepping inverter AC to 22 kV), switchgear, and LV auxiliary supply housed in a 20-foot outdoor container for simplified installation and maintenance.
-
Provides grid-compliant support functions including low/high voltage ride-through, active and reactive power control, and power ramp-rate management.
-
Includes comprehensive protection features such as DC input protection, AC output protection, surge protection, ground-fault and insulation monitoring.
Technical Specifications
DC (PV) Input
-
Maximum PV input voltage: 1500 V DC.
-
MPP voltage range: 895–1500 V.
-
Number of independent MPPTs: 4.
-
DC input configuration: up to 20 inputs (optional 28).
-
Maximum PV input current: 4 × 1435 A.
AC (Output) / Power Ratings
-
Rated AC output power (inverter): ~4400 kVA @ 45 °C.
-
Maximum AC output power: up to ~5060 kVA (lower ambient temperatures).
-
Nominal medium-voltage output: configurable between 10 kV and 35 kV (here set at 22 kV).
-
Maximum AC current: ~292.2 A.
-
Power factor (nominal/adjustable): > 0.99 / 0.8 leading – 0.8 lagging.
-
Grid frequency: 50 Hz (45–55 Hz) or 60 Hz (55–65 Hz).
Efficiency & Performance
-
Maximum inverter efficiency: ~99 %.
-
European efficiency: ~98.7 %.
-
Total harmonic distortion (THD): < 3 % at nominal power.
Transformer & Grid Interface
-
MV transformer: integrated with station; LV/MV step-up to 22 kV.
-
Transformer vector group: typically Dy11.
-
Cooling type: ONAN (oil natural, air natural).
Protection & Grid Support
-
DC input protection: load switches and fuses.
-
AC output protection: circuit breakers on inverter and MV side.
-
Surge protection: DC/AC Type II.
-
Ground-fault and insulation monitoring.
-
Low/high voltage ride-through (L/HVRT).
-
Active/reactive power control and ramp-rate control.
Physical & Environmental
-
Containerised outdoor design: ~6058 mm × 2896 mm × 2438 mm.
-
Weight: ~20 000 kg.
-
Protection class: Inverter IP65; other components IP54.
-
Operating ambient temperature: −35 °C to +60 °C.
-
Relative humidity: 0 %–100 %.
-
Cooling method: temperature-controlled forced air.
-
Maximum standard operating altitude: ~1000 m (higher with optional configuration).
Communications & Monitoring
-
Display: LED indicators and/or WebHMI.
-
Interfaces: RS485, Ethernet.
Compliance & Standards
-
Certified to CE and international standards including IEC 62109, IEC 61727, IEC 62116, IEC 62271-202, IEC 62271-200, and IEC 60076.








Reviews